Recommended lux levels for rooms, and how many lights you need

A lux is one lumen of light falling on one square metre. The recommended lux level for a room is the average light needed on its working surface for the task done there: about 500 lux for an office desk or a classroom, 300 lux for a kitchen or a study, 150–200 lux for living and dining rooms, and 100 lux for bedrooms and corridors.

Lux level table

These are the maintained averages CivilOS's lighting designer works to — the same table, from the same code, so a design made there meets the numbers on this page. U0 is the uniformity (minimum ÷ average); UGR is the glare limit where the standard sets one.

RoomAverage (Ēm)Uniformity U0Glare (UGR)Source
Living / drawing room150 lux0.4—IS 3646-1 · NBC 2016 Pt 8 (home, general)
Dining200 lux0.4—IS 3646-1 · NBC 2016 Pt 8 (home, general)
Master bedroom100 lux0.4—IS 3646-1 · NBC 2016 Pt 8 (home, general)
Bedroom100 lux0.4—IS 3646-1 · NBC 2016 Pt 8 (home, general)
Kitchen300 lux0.6—IS 3646-1 · NBC 2016 Pt 8 (home kitchen)
Toilet / bath200 lux0.4≤ 25EN 12464-1:2021 (toilets)
Corridor / passage100 lux0.4≤ 28EN 12464-1:2021 (corridors)
Staircase150 lux0.4≤ 25EN 12464-1:2021 (stairs)
Store100 lux0.4≤ 25EN 12464-1:2021 (store rooms)
Pooja room150 lux0.4—IS 3646-1 (home, general)
Study300 lux0.6≤ 19IS 3646-1 · NBC 2016 Pt 8 (study)
Office (writing, screen work)500 lux0.6≤ 19EN 12464-1:2021 (offices)
Meeting / conference500 lux0.6≤ 19EN 12464-1:2021 (conference rooms)
Classroom500 lux0.6≤ 19EN 12464-1:2021 (classrooms)
Reception / lobby200 lux0.4≤ 22EN 12464-1:2021 (entrance halls)
Shop / sales area300 lux0.4≤ 22EN 12464-1:2021 (retail)
Utility / wash area200 lux0.4—IS 3646-1 (laundry)
Parking (covered)75 lux0.4≤ 25EN 12464-1:2021 (car parks)
Balcony / sit-out50 lux0.25—design target
Warehouse / workshop200 lux0.4≤ 25EN 12464-1:2021 (stores, general)

How many lights does a room need? The lumen method

For a quick count, the lumen method gives the number of fittings:

N = (E × A) ÷ (Φ × UF × MF)

Example: an office 6 m × 5 m = 30 m², needing 500 lux, with 3,600-lumen panels, UF 0.6, MF 0.8:

N = (500 × 30) ÷ (3,600 × 0.6 × 0.8) = 8.7 → 9 panels, laid out evenly.

Why the average is not the whole story

A room can reach its average and still be badly lit: bright under the fittings and dim between them, or glaring at a screen. That is why the standards also set a uniformity (the minimum should be at least 0.4–0.6 of the average) and a glare limit. The lumen method cannot check either; a point-by-point calculation can.

The lumen method is for estimating. A design for issue should be calculated point by point with the actual fittings' photometric (IES or LDT) files and checked by a lighting designer or electrical engineer.

CivilOS's Lighting & Lux calculates every room point by point, adds the light reflected off the walls, checks lux, uniformity and glare against this table, can light every room to standard with the fewest watts, and prints a lux report.

Calculate lux in CivilOS →

Frequently asked questions

What is the recommended lux level for an office?
500 lux maintained average on the desk for writing and screen work, with a uniformity of at least 0.6 and a glare rating (UGR) of 19 or less, per EN 12464-1:2021.

What is the lux level for a bedroom?
About 100 lux general lighting, with brighter local light for reading. Living rooms are around 150 lux, kitchens 300 lux.

What is the lux level for a classroom?
500 lux on the desks, uniformity 0.6 and UGR 19, per EN 12464-1:2021.

How do I calculate the number of lights for a room?
Use the lumen method: N = (lux needed × area) ÷ (lumens per fitting × utilisation factor × maintenance factor). For a 30 m² office at 500 lux with 3,600 lm panels, UF 0.6 and MF 0.8, that is 9 panels.